Stenner S Series S30 Metering Pump
THE STENNER S SERIES PUMP INTERFACES WITH PROCESS CONTROL SYSTEMS UTILIZING A 4-20mA OUTPUT SIGNAL AND THREE RELAY OUTPUTS
Built to NEMA 4X for demanding applications. Select from multiple performance indicators and operational modes with intuitive programming and easy navigation. Fine-tune the pump to fit the application; monitor the pump for peace of mind. Prevent unauthorized access to programmed settings with the password protection.
Built solid, built to last:
The Stenner S Series pump uses a strong brushless DC motor equipped with ball bearing support.
Switch mode power supply is very energy efficient.
Totally enclosed motor is outdoor rated.
OLED operation display is easy to see in bright light and easy to navigate it's intuitive programming screens.
QuickPro pump head does not require tools to change a pump tube.
Splined shaft pump head design allows for hight torque and more reliable operation.
NEMA 4X, NSF 61 & 372, cULus indoor/outdoor, CE IP65 Ratings.
Maximum Flow Rates:
40 gpd, up to 100 psi / 151.4 lpd, up to 6.9 bar
85 gpd, up to 25 psi / 321.8 lpd, up to 1.7 bar
Smart Technology Modes and Indicators:
OLED Display
Tube Leak Detection
Tube Change Timer
Standby Mode
Repeat Pulse Mode
Run Mode
Mode Change Interface
High and Low Signal Indicator
High and Low Flow Indicator
Drive Fault Indicator
Signal Overrun Indicator
Transfer Mode
Off Mode
Tube Leak Detection Built Into The Pump Head
Detects fluid in the pump head, vertically or horizontally
Stops pump on leak detection with alarm relay output
Calibrate sensitivity to specific fluid being used. Stops false alarms caused by humidity or substance.
Tube timer:
Set a maintenance interval to let you know when it's time to change the tube before it breaks.
Standby Mode:
Program the transfer mode to activate a relay to start a second Stenner S Series Pump. Great for redundancy and failover should one pump be down for maintenance.
Signal Inputs:
4-20 mA Signal: Proportional response to the analog signal, scalable, invertible,speed varies to the input signal
0-10VDC Signal: Proportional response to the analog signal, scalable, invertible,speed varies to the input signal
Pulse: Accepts dry contact or open collector input signal from water meter or controllers, activates pump at desired pulse count to run for a specified amount of time.
Hall Effect: Speed varies according to Hall Effect input from flow meter or controller, program based on K factor, process flow range and desired pump output.
PPM Feed Constant Flow: Accepts a dry contact or open collector type input signal from flow switch. Program is based on the process flow rate, chemical concentration, chemical specific gravity and the desired ppm feed rate.
PPM Feed Variable Flow: Accepts a Hall Effect input from a flow meter. Speed varies based on process flow rate. Program based on K factor, process flow range, chemical concentration, specific gravity and desired ppm feed rate.
Manual Operation:
Manual: Speed controlled manually. Adjustable from 0% to 100% in 1% increments
7 Day / 24 Hour Timer: Run on a specific day, time of day, at speeds from 1 to 100%. 24 Independent events, any combination of days.
Cycle Timer: Run on a repeating on/off cycle. Set peristaltic pump speed from 1 to 100%
Signal Outputs:
4-20 mA output, produces a non-adjustable signal output that is proportional to the Stenner pump speed percentage the pump is running. 4mA = 0% & 20mA = 100%.
Relays dry contact programed to either normally open or normally closed. Indicate alarms, repeat and incoming signal, transfer operation to another S series pump that is in Standby.
SKU
S300
WEIGHT:
9.00 LBS
SHIPPING:
Calculated at checkout.